Electrical Wire Sizes for Conduit Fill
Conduit fill calculations depend on the cross-sectional area of each conductor, which includes both the metal conductor and its insulation. Different insulation types (THHN/THWN-2, THWN, XHHW, USE-2) have different thicknesses, resulting in different overall areas for the same wire gauge. This page lists the NEC Chapter 9, Table 5 areas for all supported conductor types and sizes, from 14 AWG through 500 kcmil.
Wire sizes are specified using two systems: AWG (American Wire Gauge) for smaller conductors from 14 AWG through 4/0 AWG, and kcmil (thousand circular mils) for larger conductors starting at 250 kcmil. In the AWG system, smaller numbers indicate larger conductors: 14 AWG is smaller than 12 AWG, which is smaller than 10 AWG. The 4/0 AWG size (sometimes written as "0000") is the largest AWG designation. Beyond that, sizes are specified in kcmil, where larger numbers indicate larger conductors.
Each conductor type below links to a dedicated guide page with minimum conduit size tables, detailed specifications, and application guidance. Click the wire type name to view the full guide, or use the comparison table at the bottom of this page to see how insulation type affects conduit fill.
THHN/THWN-2 Conductors
| Wire Size | Area (sq.in.) | Typical Ampacity | Common Application |
|---|---|---|---|
| 14 AWG | 0.0097 | 15A | Lighting circuits, small appliance circuits, and general-purpose 15-amp branch circuits. The minimum size permitted for building wiring under NEC Article 210. |
| 12 AWG | 0.0133 | 20A | Standard receptacle circuits, kitchen circuits, bathroom circuits, and general-purpose 20-amp branch circuits. The most commonly installed wire size in residential construction. |
| 10 AWG | 0.0211 | 30A | Electric dryers, window air conditioners, water heaters, and 30-amp dedicated circuits. Also used for long-run 20-amp circuits where voltage drop is a concern. |
| 8 AWG | 0.0366 | 40-50A | Electric ranges, large air conditioning units, hot tubs, and welders. Used for 40-amp and 50-amp branch circuits. |
| 6 AWG | 0.0507 | 55-65A | Subpanels, large motors, EV chargers, and 60-amp feeder circuits. Common for residential subpanel feeders. |
| 4 AWG | 0.0824 | 70-85A | Service entrance conductors for small residential services, large subpanels, and high-amperage feeders. |
| 3 AWG | 0.0973 | 85-100A | 100-amp service entrance and feeders. Common for residential main service conductors. |
| 2 AWG | 0.1158 | 95-115A | 100-amp to 110-amp services and feeders. Used for residential service entrance conductors. |
| 1 AWG | 0.1562 | 110-130A | Large residential service entrance, commercial feeders, and high-amperage distribution circuits. |
| 1/0 AWG | 0.1855 | 125-150A | 150-amp service entrance, large commercial feeders, and residential main service upgrades. |
| 2/0 AWG | 0.2223 | 145-175A | 175-amp services, commercial building feeders, and industrial distribution. |
| 3/0 AWG | 0.2679 | 165-200A | 200-amp residential main service entrance. The standard size for modern home main services. |
| 4/0 AWG | 0.3237 | 195-230A | 200-amp to 225-amp services with adequate headroom. Also used for large commercial feeders. |
| 250 AWG | 0.3970 | 215-255A | Large commercial services, industrial feeders, and high-capacity distribution runs. |
| 300 AWG | 0.4608 | 240-285A | Commercial building main services, industrial distribution, and paralleled feeder runs. |
| 350 AWG | 0.5242 | 260-310A | Large commercial and industrial services. Often used in paralleled configurations. |
| 400 AWG | 0.5863 | 280-335A | Industrial main services, large commercial buildings, and utility interconnections. |
| 500 AWG | 0.7073 | 305-380A | Heavy industrial feeders, large commercial services, and power plant distribution. Typically requires 2-inch or larger conduit. |
View complete THHN/THWN-2 conduit fill guide with minimum conduit sizes
THWN Conductors
| Wire Size | Area (sq.in.) | Typical Ampacity | Common Application |
|---|---|---|---|
| 14 AWG | 0.0097 | 15A | Lighting circuits, small appliance circuits, and general-purpose 15-amp branch circuits. The minimum size permitted for building wiring under NEC Article 210. |
| 12 AWG | 0.0133 | 20A | Standard receptacle circuits, kitchen circuits, bathroom circuits, and general-purpose 20-amp branch circuits. The most commonly installed wire size in residential construction. |
| 10 AWG | 0.0211 | 30A | Electric dryers, window air conditioners, water heaters, and 30-amp dedicated circuits. Also used for long-run 20-amp circuits where voltage drop is a concern. |
| 8 AWG | 0.0366 | 40-50A | Electric ranges, large air conditioning units, hot tubs, and welders. Used for 40-amp and 50-amp branch circuits. |
| 6 AWG | 0.0507 | 55-65A | Subpanels, large motors, EV chargers, and 60-amp feeder circuits. Common for residential subpanel feeders. |
| 4 AWG | 0.0824 | 70-85A | Service entrance conductors for small residential services, large subpanels, and high-amperage feeders. |
| 3 AWG | 0.0973 | 85-100A | 100-amp service entrance and feeders. Common for residential main service conductors. |
| 2 AWG | 0.1158 | 95-115A | 100-amp to 110-amp services and feeders. Used for residential service entrance conductors. |
| 1 AWG | 0.1562 | 110-130A | Large residential service entrance, commercial feeders, and high-amperage distribution circuits. |
| 1/0 AWG | 0.1855 | 125-150A | 150-amp service entrance, large commercial feeders, and residential main service upgrades. |
| 2/0 AWG | 0.2223 | 145-175A | 175-amp services, commercial building feeders, and industrial distribution. |
| 3/0 AWG | 0.2679 | 165-200A | 200-amp residential main service entrance. The standard size for modern home main services. |
| 4/0 AWG | 0.3237 | 195-230A | 200-amp to 225-amp services with adequate headroom. Also used for large commercial feeders. |
| 250 AWG | 0.3970 | 215-255A | Large commercial services, industrial feeders, and high-capacity distribution runs. |
| 300 AWG | 0.4608 | 240-285A | Commercial building main services, industrial distribution, and paralleled feeder runs. |
| 350 AWG | 0.5242 | 260-310A | Large commercial and industrial services. Often used in paralleled configurations. |
| 400 AWG | 0.5863 | 280-335A | Industrial main services, large commercial buildings, and utility interconnections. |
| 500 AWG | 0.7073 | 305-380A | Heavy industrial feeders, large commercial services, and power plant distribution. Typically requires 2-inch or larger conduit. |
View complete THWN conduit fill guide with minimum conduit sizes
XHHW Conductors
| Wire Size | Area (sq.in.) | Typical Ampacity | Common Application |
|---|---|---|---|
| 14 AWG | 0.0139 | 15A | Lighting circuits, small appliance circuits, and general-purpose 15-amp branch circuits. The minimum size permitted for building wiring under NEC Article 210. |
| 12 AWG | 0.0181 | 20A | Standard receptacle circuits, kitchen circuits, bathroom circuits, and general-purpose 20-amp branch circuits. The most commonly installed wire size in residential construction. |
| 10 AWG | 0.0243 | 30A | Electric dryers, window air conditioners, water heaters, and 30-amp dedicated circuits. Also used for long-run 20-amp circuits where voltage drop is a concern. |
| 8 AWG | 0.0437 | 40-50A | Electric ranges, large air conditioning units, hot tubs, and welders. Used for 40-amp and 50-amp branch circuits. |
| 6 AWG | 0.0590 | 55-65A | Subpanels, large motors, EV chargers, and 60-amp feeder circuits. Common for residential subpanel feeders. |
| 4 AWG | 0.0814 | 70-85A | Service entrance conductors for small residential services, large subpanels, and high-amperage feeders. |
| 3 AWG | 0.0962 | 85-100A | 100-amp service entrance and feeders. Common for residential main service conductors. |
| 2 AWG | 0.1146 | 95-115A | 100-amp to 110-amp services and feeders. Used for residential service entrance conductors. |
| 1 AWG | 0.1534 | 110-130A | Large residential service entrance, commercial feeders, and high-amperage distribution circuits. |
| 1/0 AWG | 0.1825 | 125-150A | 150-amp service entrance, large commercial feeders, and residential main service upgrades. |
| 2/0 AWG | 0.2190 | 145-175A | 175-amp services, commercial building feeders, and industrial distribution. |
| 3/0 AWG | 0.2642 | 165-200A | 200-amp residential main service entrance. The standard size for modern home main services. |
| 4/0 AWG | 0.3197 | 195-230A | 200-amp to 225-amp services with adequate headroom. Also used for large commercial feeders. |
| 250 AWG | 0.3904 | 215-255A | Large commercial services, industrial feeders, and high-capacity distribution runs. |
| 300 AWG | 0.4536 | 240-285A | Commercial building main services, industrial distribution, and paralleled feeder runs. |
| 350 AWG | 0.5166 | 260-310A | Large commercial and industrial services. Often used in paralleled configurations. |
| 400 AWG | 0.5782 | 280-335A | Industrial main services, large commercial buildings, and utility interconnections. |
| 500 AWG | 0.6984 | 305-380A | Heavy industrial feeders, large commercial services, and power plant distribution. Typically requires 2-inch or larger conduit. |
View complete XHHW conduit fill guide with minimum conduit sizes
USE-2 Conductors
| Wire Size | Area (sq.in.) | Typical Ampacity | Common Application |
|---|---|---|---|
| 14 AWG | 0.0139 | 15A | Lighting circuits, small appliance circuits, and general-purpose 15-amp branch circuits. The minimum size permitted for building wiring under NEC Article 210. |
| 12 AWG | 0.0181 | 20A | Standard receptacle circuits, kitchen circuits, bathroom circuits, and general-purpose 20-amp branch circuits. The most commonly installed wire size in residential construction. |
| 10 AWG | 0.0243 | 30A | Electric dryers, window air conditioners, water heaters, and 30-amp dedicated circuits. Also used for long-run 20-amp circuits where voltage drop is a concern. |
| 8 AWG | 0.0437 | 40-50A | Electric ranges, large air conditioning units, hot tubs, and welders. Used for 40-amp and 50-amp branch circuits. |
| 6 AWG | 0.0590 | 55-65A | Subpanels, large motors, EV chargers, and 60-amp feeder circuits. Common for residential subpanel feeders. |
| 4 AWG | 0.0814 | 70-85A | Service entrance conductors for small residential services, large subpanels, and high-amperage feeders. |
| 3 AWG | 0.0962 | 85-100A | 100-amp service entrance and feeders. Common for residential main service conductors. |
| 2 AWG | 0.1146 | 95-115A | 100-amp to 110-amp services and feeders. Used for residential service entrance conductors. |
| 1 AWG | 0.1534 | 110-130A | Large residential service entrance, commercial feeders, and high-amperage distribution circuits. |
| 1/0 AWG | 0.1825 | 125-150A | 150-amp service entrance, large commercial feeders, and residential main service upgrades. |
| 2/0 AWG | 0.2190 | 145-175A | 175-amp services, commercial building feeders, and industrial distribution. |
| 3/0 AWG | 0.2642 | 165-200A | 200-amp residential main service entrance. The standard size for modern home main services. |
| 4/0 AWG | 0.3197 | 195-230A | 200-amp to 225-amp services with adequate headroom. Also used for large commercial feeders. |
| 250 AWG | 0.3904 | 215-255A | Large commercial services, industrial feeders, and high-capacity distribution runs. |
| 300 AWG | 0.4536 | 240-285A | Commercial building main services, industrial distribution, and paralleled feeder runs. |
| 350 AWG | 0.5166 | 260-310A | Large commercial and industrial services. Often used in paralleled configurations. |
| 400 AWG | 0.5782 | 280-335A | Industrial main services, large commercial buildings, and utility interconnections. |
| 500 AWG | 0.6984 | 305-380A | Heavy industrial feeders, large commercial services, and power plant distribution. Typically requires 2-inch or larger conduit. |
View complete USE-2 conduit fill guide with minimum conduit sizes
Wire Size Comparison Across Insulation Types
The table below shows how cross-sectional area varies by insulation type for each wire gauge. THHN/THWN-2 conductors are generally the smallest due to their thin nylon-jacketed PVC insulation, while XHHW and USE-2 are larger due to their thicker cross-linked polyethylene insulation. Choosing THHN/THWN-2 when permitted maximizes the number of conductors that fit in a given conduit size.
| Wire Size | THHN/THWN-2 (sq.in.) | THWN (sq.in.) | XHHW (sq.in.) | USE-2 (sq.in.) |
|---|---|---|---|---|
| 14 AWG | 0.0097 | 0.0097 | 0.0139 | 0.0139 |
| 12 AWG | 0.0133 | 0.0133 | 0.0181 | 0.0181 |
| 10 AWG | 0.0211 | 0.0211 | 0.0243 | 0.0243 |
| 8 AWG | 0.0366 | 0.0366 | 0.0437 | 0.0437 |
| 6 AWG | 0.0507 | 0.0507 | 0.0590 | 0.0590 |
| 4 AWG | 0.0824 | 0.0824 | 0.0814 | 0.0814 |
| 3 AWG | 0.0973 | 0.0973 | 0.0962 | 0.0962 |
| 2 AWG | 0.1158 | 0.1158 | 0.1146 | 0.1146 |
| 1 AWG | 0.1562 | 0.1562 | 0.1534 | 0.1534 |
| 1/0 AWG | 0.1855 | 0.1855 | 0.1825 | 0.1825 |
| 2/0 AWG | 0.2223 | 0.2223 | 0.2190 | 0.2190 |
| 3/0 AWG | 0.2679 | 0.2679 | 0.2642 | 0.2642 |
| 4/0 AWG | 0.3237 | 0.3237 | 0.3197 | 0.3197 |
| 250 AWG | 0.3970 | 0.3970 | 0.3904 | 0.3904 |
| 300 AWG | 0.4608 | 0.4608 | 0.4536 | 0.4536 |
| 350 AWG | 0.5242 | 0.5242 | 0.5166 | 0.5166 |
| 400 AWG | 0.5863 | 0.5863 | 0.5782 | 0.5782 |
| 500 AWG | 0.7073 | 0.7073 | 0.6984 | 0.6984 |